No advisories yet.
Solution
No solution given by the vendor.
Workaround
Users are recommended to take the following mitigation measures: * Enable the IP Filter feature: Configure and enable the PLC's built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access. * Set up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device's core control logic and parameters cannot be easily downloaded, overwritten, or tampered with. * Implement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel.
Tue, 30 Jun 2026 07:15:00 +0000
| Type | Values Removed | Values Added |
|---|---|---|
| Description | Delta Electronics DVP12SE PLC exposes a Modbus TCP service over a specified port without authentication or access control, permitting unauthenticated interaction with security-sensitive PLC functions. | |
| Title | DVP-12SE Missing Authentication and Unauthorized Write access Vulnerability | |
| First Time appeared |
Deltaww
Deltaww dvp-12se |
|
| Weaknesses | CWE-306 | |
| CPEs | cpe:2.3:a:deltaww:dvp-12se:*:*:*:*:*:*:*:* | |
| Vendors & Products |
Deltaww
Deltaww dvp-12se |
|
| References |
| |
| Metrics |
cvssV4_0
|
Projects
Sign in to view the affected projects.
Status: PUBLISHED
Assigner: Deltaww
Published:
Updated: 2026-06-30T06:28:51.514Z
Reserved: 2026-06-21T10:18:28.804Z
Link: CVE-2026-12819
No data.
No data.
No data.
OpenCVE Enrichment
Updated: 2026-06-30T08:30:04Z