| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually. |
| Siemens LOGO! Soft Comfort (All versions before V8.2) lacks integrity verification of software packages downloaded via an unprotected communication channel. This could allow a remote attacker to manipulate the software package while performing a Man-in-the-Middle (MitM) attack. |
| An issue was discovered on Siemens SICAM RTUs SM-2556 COM Modules with the firmware variants ENOS00, ERAC00, ETA2, ETLS00, MODi00, and DNPi00. The integrated web server (port 80/tcp) of the affected devices could allow unauthenticated remote attackers to execute arbitrary code on the affected device. |
| The decodenetnum function in ntpd in NTP 4.2.x before 4.2.8p4, and 4.3.x before 4.3.77 allows remote attackers to cause a denial of service (assertion failure) via a 6 or mode 7 packet containing a long data value. |
| Siemens SIMATIC Logon prior to V1.5 SP3 Update 2 could allow an attacker with knowledge of a valid user name, and physical or network access to the affected system, to bypass the application-level authentication. |
| An issue was discovered in Siemens SICAM PAS before 8.00. Because of Storing Passwords in a Recoverable Format, an authenticated local attacker with certain privileges could possibly reconstruct the passwords of users for accessing the database. |
| An issue was discovered in Siemens ETA4 firmware (all versions prior to Revision 08) of the SM-2558 extension module for: SICAM AK, SICAM TM 1703, SICAM BC 1703, and SICAM AK 3. Specially crafted packets sent to Port 2404/TCP could cause the affected device to go into defect mode. A cold start might be required to recover the system, a Denial-of-Service Vulnerability. |
| Siemens RUGGEDCOM ROX I (all versions) allow an authenticated user to bypass access restrictions in the web interface at port 10000/TCP to obtain privileged file system access or change configuration settings. |
| The integrated web server in Siemens RUGGEDCOM ROX I (all versions) at port 10000/TCP could allow remote attackers to perform actions with the privileges of an authenticated user, provided the targeted user has an active session and is induced into clicking on a malicious link or into visiting a malicious website, aka CSRF. |
| Siemens RUGGEDCOM ROX I (all versions) contain a vulnerability in the integrated web server at port 10000/TCP which is prone to reflected Cross-Site Scripting attacks if an unsuspecting user is induced to click on a malicious link. |
| Siemens RUGGEDCOM ROX I (all versions) contain a vulnerability that could allow an authenticated user to read arbitrary files through the web interface at port 10000/TCP and access sensitive information. |
| Siemens SINUMERIK Integrate Operate Clients between 2.0.3.00.016 (including) and 2.0.6 (excluding) and between 3.0.4.00.032 (including) and 3.0.6 (excluding) contain a vulnerability that could allow an attacker to read and manipulate data in TLS sessions while performing a man-in-the-middle (MITM) attack. |
| A non-privileged user of the Siemens web application RUGGEDCOM NMS < V1.2 on port 8080/TCP and 8081/TCP could perform a persistent Cross-Site Scripting (XSS) attack, potentially resulting in obtaining administrative permissions. |
| The Siemens web application RUGGEDCOM NMS < V1.2 on port 8080/TCP and 8081/TCP could allow a remote attacker to perform a Cross-Site Request Forgery (CSRF) attack, potentially allowing an attacker to execute administrative operations, provided the targeted user has an active session and is induced to trigger a malicious request. |
| Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected. |
| Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected. |
| ntpd in NTP before 4.2.8p6 and 4.3.x before 4.3.90 allows remote attackers to cause a denial of service (NULL pointer dereference) via a ntpdc reslist command. |
| A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations. |
| A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 Ready4Linux (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packet over port 102/tcp. A restart of the affected device is needed to restore normal operations. |
| A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations. |