| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| A vulnerability has been identified in SIMATIC IPC DiagBase (All versions), SIMATIC IPC DiagMonitor (All versions). The affected device do not properly restrict the user permission for the registry key. This could allow an authenticated attacker to load vulnerable drivers into the system leading to privilege escalation or bypassing endpoint protection and other security measures. |
| A vulnerability has been identified in SIMATIC Virtualization as a Service (SIVaaS) (All versions). The affected application exposes a network share without any authentication. This could allow an attacker to access or alter sensitive data without proper authorization. |
| A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). Affected application contains a hidden configuration item to enable debug functionality. This could allow an authenticated local attacker to gain insight into the internal configuration of the deployment. |
| A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.3), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.3). The web server interface of affected devices improperly processes incoming malformed HTTP traffic at high rate. This could allow an unauthenticated remote attacker to force the device entering the stop/defect state, thus creating a denial of service condition. |
| A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state.
This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation. |
| A vulnerability has been identified in SIMATIC Energy Manager Basic (All versions < V7.5), SIMATIC Energy Manager PRO (All versions < V7.5), SIMATIC IPC DiagBase (All versions), SIMATIC IPC DiagMonitor (All versions), SIMIT V10 (All versions), SIMIT V11 (All versions < V11.1). Unified Automation .NET based OPC UA Server SDK before 3.2.2 used in Siemens products are affected by a similar vulnerability as documented in CVE-2023-27321 for the OPC Foundation UA .NET Standard implementation. A successful attack may lead to high load situation and memory exhaustion, and may block the server. |
| Affected devices contain a vulnerability that allows an unauthenticated attacker to trigger a denial of service condition. The vulnerability can be triggered if a large amount of DCP reset packets are sent to the device. |
| Affected devices do not properly sanitize contents of trace files.
This could allow an attacker to inject code through social engineering an authorized user, who has the function right "Read diagnostics", to import a specially crafted trace file.
The malicious trace file is insufficiently sanitized and malicious code could be executed in the clients browser session and trigger PLC operations via the webserver that the legitimate user is authorized to perform. |
| A vulnerability has been identified in SIMATIC PC-Station Plus (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions), SINAMICS S120 (incl. SIPLUS variants) (All versions < V5.2 SP3 HF15), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions). The affected products do not handle HTTP(S) requests to the web server correctly.
This could allow an attacker to exhaust system resources and create a denial of service condition for the device. |
| Affected devices improperly handle specially crafted packets sent to port 102/tcp.
This could allow an attacker to create a denial of service condition. A restart is needed to restore
normal operations. |
| A vulnerability has been identified in Opcenter Execution Foundation (All versions < V2407), Opcenter Quality (All versions < V2312), SIMATIC PCS neo (All versions < V4.1), SINEC NMS (All versions < V2.0 SP1), Totally Integrated Automation Portal (TIA Portal) V14 (All versions), Totally Integrated Automation Portal (TIA Portal) V15.1 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 8), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 3). The affected application contains an out of bounds write past the end of an allocated buffer when handling specific requests on port 4002/tcp and 4004/tcp. This could allow an attacker to crash the application. The corresponding service is auto-restarted after the crash. |
| A vulnerability has been identified in SIMATIC CN 4100 (All versions < V2.5). Affected device consists of an incorrect default value in the SSH configuration. This could allow an attacker to bypass network isolation. |
| A vulnerability has been identified in SIMATIC CN 4100 (All versions < V2.5). Affected device consists of improper access controls in the configuration files that leads to privilege escalation. An attacker could gain admin access with this vulnerability leading to complete device control. |
| A vulnerability has been identified in SIMATIC CN 4100 (All versions < V4.0). The affected application allows to control the device by storing arbitrary files in the SFTP folder of the device. This could allow an attacker to cause a denial of service condition. |
| A vulnerability has been identified in SIMATIC CN 4100 (All versions < V2.7). The "intermediate installation" system state of the affected application allows an attacker to add their own login credentials to the device. This allows an attacker to remotely login as root and take control of the device even after the affected device is fully set up. |
| A vulnerability has been identified in SIMATIC CN 4100 (All versions < V2.7). The "intermediate installation" system state of the affected application uses default credential with admin privileges. An attacker could use the credentials to gain complete control of the affected device. |
| A vulnerability has been identified in SIMATIC CN 4100 (All versions < V2.7). The affected application allows IP configuration change without authentication to the device. This could allow an attacker to cause denial of service condition. |
| A vulnerability has been identified in SIMATIC CN 4100 (All versions < V4.0.1). The affected device contains a USB port which allows unauthenticated connections. This could allow an attacker with physical access to the device to trigger reboot that could cause denial of service condition. |
| A vulnerability has been identified in SIMATIC CN 4100 (All versions < V4.0.1). The affected application do not properly validate input parameters in its REST API, resulting in improper handling of unexpected arguments.
This could allow an authenticated attacker to execute arbitrary code with limited privileges. |
| A vulnerability has been identified in SIMATIC CN 4100 (All versions < V4.0.1). The affected device stores sensitive information in the firmware. This could allow an attacker to access and misuse this information, potentially impacting the device’s confidentiality, integrity, and availability. |