| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| A vulnerability has been identified in SIMATIC Virtualization as a Service (SIVaaS) (All versions). The affected application exposes a network share without any authentication. This could allow an attacker to access or alter sensitive data without proper authorization. |
| A vulnerability has been identified in Desigo CC (All versions if access from Installed Clients to Desigo CC server is allowed from networks outside of a highly protected zone), Desigo CC (All versions if access from Installed Clients to Desigo CC server is only allowed within highly protected zones). The affected server application fails to authenticate specific client requests. Modification of the client binary could allow an unauthenticated remote attacker to execute arbitrary SQL queries on the server database via the event port (default: 4998/tcp) |
| A vulnerability has been identified in CPC80 Central Processing/Communication (All versions < V16.41), CPCI85 Central Processing/Communication (All versions < V5.30), CPCX26 Central Processing/Communication (All versions < V06.02), ETA4 Ethernet Interface IEC60870-5-104 (All versions < V10.46), ETA5 Ethernet Int. 1x100TX IEC61850 Ed.2 (All versions < V03.27), PCCX26 Ax 1703 PE, Contr, Communication Element (All versions < V06.05). The affected devices contain an improper null termination vulnerability while parsing a specific HTTP header. This could allow an attacker to execute code in the context of the current process or lead to denial of service condition. |
| A vulnerability has been identified in SIMATIC STEP 7 Safety V18 (All versions < V18 Update 2). Affected applications do not properly restrict the .NET BinaryFormatter when deserializing user-controllable input. This could allow an attacker to cause a type confusion and execute arbitrary code within the affected application.
This is the same issue that exists for .NET BinaryFormatter https://docs.microsoft.com/en-us/visualstudio/code-quality/ca2300. |
| A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions), Cerberus PRO EN Fire Panel FC72x IP6 (All versions), Cerberus PRO EN Fire Panel FC72x IP7 (All versions), Cerberus PRO EN Fire Panel FC72x IP8 (All versions < IP8 SR4), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.3.5618), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.3.5617), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions), Sinteso FS20 EN Fire Panel FC20 MP8 (All versions < MP8 SR4), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.3.5618), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.3.5617), Sinteso Mobile (All versions). The network communication library in affected systems improperly handles memory buffers when parsing X.509 certificates.
This could allow an unauthenticated remote attacker to crash the network service. |
| A vulnerability has been identified in SIMATIC STEP 7 Safety V16 (All versions < V16 Update 7), SIMATIC STEP 7 Safety V17 (All versions < V17 Update 7), SIMATIC STEP 7 Safety V18 (All versions < V18 Update 2), SIMATIC STEP 7 V16 (All versions < V16 Update 7), SIMATIC STEP 7 V17 (All versions < V17 Update 7), SIMATIC STEP 7 V18 (All versions < V18 Update 2), SIMATIC WinCC Unified V16 (All versions < V16 Update 7), SIMATIC WinCC Unified V17 (All versions < V17 Update 7), SIMATIC WinCC Unified V18 (All versions < V18 Update 2), SIMATIC WinCC V16 (All versions < V16.7), SIMATIC WinCC V17 (All versions < V17.7), SIMATIC WinCC V18 (All versions < V18 Update 2), SIMOCODE ES V16 (All versions < V16 Update 7), SIMOCODE ES V17 (All versions < V17 Update 7), SIMOCODE ES V18 (All versions < V18 Update 2), SIMOTION SCOUT TIA V5.4 SP1 (All versions), SIMOTION SCOUT TIA V5.4 SP3 (All versions), SIMOTION SCOUT TIA V5.5 SP1 (All versions), SINAMICS Startdrive V16 (All versions), SINAMICS Startdrive V17 (All versions), SINAMICS Startdrive V18 (All versions), SIRIUS Safety ES V17 (All versions < V17 Update 7), SIRIUS Safety ES V18 (All versions < V18 Update 2), SIRIUS Soft Starter ES V17 (All versions < V17 Update 7), SIRIUS Soft Starter ES V18 (All versions < V18 Update 2), Soft Starter ES V16 (All versions < V16 Update 7), TIA Portal Cloud V3.0 (All versions < V18 Update 2). Affected applications do not properly restrict the .NET BinaryFormatter when deserializing hardware configuration profiles. This could allow an attacker to cause a type confusion and execute arbitrary code within the affected application.
This is the same issue that exists for .NET BinaryFormatter https://docs.microsoft.com/en-us/visualstudio/code-quality/ca2300. |
| A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions), Cerberus PRO EN Fire Panel FC72x IP6 (All versions), Cerberus PRO EN Fire Panel FC72x IP7 (All versions), Cerberus PRO EN Fire Panel FC72x IP8 (All versions < IP8 SR4), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.3.5618), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.3.5617), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions), Sinteso FS20 EN Fire Panel FC20 MP8 (All versions < MP8 SR4), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.3.5618), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.3.5617), Sinteso Mobile (All versions). The network communication library in affected systems insufficiently validates HMAC values which might result in a buffer overread.
This could allow an unauthenticated remote attacker to crash the network service. |
| A vulnerability has been identified in LOGO! 12/24RCE (6ED1052-1MD08-0BA2) (All versions), LOGO! 12/24RCEo (6ED1052-2MD08-0BA2) (All versions), LOGO! 230RCE (6ED1052-1FB08-0BA2) (All versions), LOGO! 230RCEo (6ED1052-2FB08-0BA2) (All versions), LOGO! 24CE (6ED1052-1CC08-0BA2) (All versions), LOGO! 24CEo (6ED1052-2CC08-0BA2) (All versions), LOGO! 24RCE (6ED1052-1HB08-0BA2) (All versions), LOGO! 24RCEo (6ED1052-2HB08-0BA2) (All versions), SIPLUS LOGO! 12/24RCE (6AG1052-1MD08-7BA2) (All versions), SIPLUS LOGO! 12/24RCEo (6AG1052-2MD08-7BA2) (All versions), SIPLUS LOGO! 230RCE (6AG1052-1FB08-7BA2) (All versions), SIPLUS LOGO! 230RCEo (6AG1052-2FB08-7BA2) (All versions), SIPLUS LOGO! 24CE (6AG1052-1CC08-7BA2) (All versions), SIPLUS LOGO! 24CEo (6AG1052-2CC08-7BA2) (All versions), SIPLUS LOGO! 24RCE (6AG1052-1HB08-7BA2) (All versions), SIPLUS LOGO! 24RCEo (6AG1052-2HB08-7BA2) (All versions). Affected devices do not conduct certain validations when interacting with them. This could allow an unauthenticated remote attacker to manipulate the devices IP address, which means the device would not be reachable. |
| A vulnerability has been identified in SiPass integrated AC5102 (ACC-G2) (All versions < V6.4.8), SiPass integrated ACC-AP (All versions < V6.4.8). Affected devices expose several MQTT URLs without authentication. This could allow an unauthenticated remote attacker to access sensitive data. |
| A vulnerability has been identified in Spectrum Power 4 (All versions < V4.70 SP12 Update 2). The affected application is vulnerable to a local privilege escalation due to an exposed debug interface on the localhost. This allows any local user to gain code execution as administrative application user. |
| A vulnerability has been identified in SIMATIC PCS neo V4.0 (All versions), SIMATIC STEP 7 V16 (All versions), SIMATIC STEP 7 V17 (All versions), SIMATIC STEP 7 V18 (All versions < V18 Update 2). Affected applications do not properly restrict the .NET BinaryFormatter when deserializing user-controllable input. This could allow an attacker to cause a type confusion and execute arbitrary code within the affected application.
This is the same issue that exists for .NET BinaryFormatter https://docs.microsoft.com/en-us/visualstudio/code-quality/ca2300. |
| A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions < V5.30), SICORE Base system (All versions < V1.3.0). The web interface of affected devices is vulnerable to command injection due to missing server side input sanitation. This could allow an authenticated privileged remote attacker to execute arbitrary code with root privileges. |
| A vulnerability has been identified in Opcenter Quality (All versions < V2406), Opcenter RDnL (All versions < V2410), SIMATIC PCS neo V4.0 (All versions), SIMATIC PCS neo V4.1 (All versions < V4.1 Update 2), SIMATIC PCS neo V5.0 (All versions < V5.0 Update 1), SINEC NMS (All versions), SINEMA Remote Connect Client (All versions < V3.2 SP3), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 8), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 5), Totally Integrated Automation Portal (TIA Portal) V19 (All versions < V19 Update 3). Affected products contain a heap-based buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to execute arbitrary code. |
| A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). Affected application contains a hidden configuration item to enable debug functionality. This could allow an authenticated local attacker to gain insight into the internal configuration of the deployment. |
| A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). Affected SIMATIC RTLS Locating Manager Track Viewer Client do not properly protect credentials that are used to authenticate to the server. This could allow an authenticated local attacker to extract the credentials and use them to escalate their access rights from the Manager to the Systemadministrator role. |
| A vulnerability has been identified in SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.3), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.3), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.3), SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.4.8), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.4.8). The web server of affected products, if configured to allow the import of PKCS12 containers, could end up in an infinite loop when processing incomplete certificate chains.
This could allow an authenticated remote attacker to create a denial of service condition by importing specially crafted PKCS12 containers. |
| A vulnerability has been identified in SIMATIC RTLS Locating Manager (6GT2780-0DA00) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-0DA30) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA10) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA20) (All versions < V3.0.1.1), SIMATIC RTLS Locating Manager (6GT2780-1EA30) (All versions < V3.0.1.1). Affected SIMATIC RTLS Locating Manager Report Clients do not properly protect credentials that are used to authenticate to the server. This could allow an authenticated local attacker to extract the credentials and use them to escalate their access rights from the Manager to the Systemadministrator role. |
| A vulnerability has been identified in Mendix Runtime V10 (All versions < V10.17.0 only if the basic authentication mechanism is used by the application), Mendix Runtime V10.12 (All versions < V10.12.11 only if the basic authentication mechanism is used by the application), Mendix Runtime V10.6 (All versions < V10.6.19 only if the basic authentication mechanism is used by the application), Mendix Runtime V8 (All versions < V8.18.33 only if the basic authentication mechanism is used by the application), Mendix Runtime V9 (All versions < V9.24.31 only if the basic authentication mechanism is used by the application). The authentication mechanism of affected applications contains an observable response discrepancy vulnerability when validating usernames. This could allow unauthenticated remote attackers to distinguish between valid and invalid usernames. |
| A vulnerability has been identified in SIMATIC S7-200 SMART CPU CR40 (6ES7288-1CR40-0AA0) (All versions), SIMATIC S7-200 SMART CPU CR60 (6ES7288-1CR60-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR20 (6ES7288-1SR20-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR20 (6ES7288-1SR20-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR30 (6ES7288-1SR30-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR30 (6ES7288-1SR30-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR40 (6ES7288-1SR40-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR40 (6ES7288-1SR40-0AA1) (All versions), SIMATIC S7-200 SMART CPU SR60 (6ES7288-1SR60-0AA0) (All versions), SIMATIC S7-200 SMART CPU SR60 (6ES7288-1SR60-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST20 (6ES7288-1ST20-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST20 (6ES7288-1ST20-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST30 (6ES7288-1ST30-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST30 (6ES7288-1ST30-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST40 (6ES7288-1ST40-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST40 (6ES7288-1ST40-0AA1) (All versions), SIMATIC S7-200 SMART CPU ST60 (6ES7288-1ST60-0AA0) (All versions), SIMATIC S7-200 SMART CPU ST60 (6ES7288-1ST60-0AA1) (All versions). Affected devices do not properly handle TCP packets with an incorrect structure. This could allow an unauthenticated remote attacker to cause a denial of service condition. To restore normal operations, the network cable of the device needs to be unplugged and re-plugged. |
| A vulnerability has been identified in Automation License Manager V5 (All versions), Automation License Manager V6.0 (All versions < V6.0 SP12 Upd3), Automation License Manager V6.2 (All versions < V6.2 Upd3). Affected applications do not properly validate certain fields in incoming network packets on port 4410/tcp. This could allow an unauthenticated remote attacker to cause an integer overflow and crash of the application. This denial of service condition could prevent legitimate users from using subsequent products that rely on the affected application for license verification. |